The leading engineering solution provider in Bangladesh with local competence.
The Series 500, four pass dry back boilers are designed for optimum fuel efficiency.

BOILER SPECIFICATIONS (ALL DIMENSIONS ARE IN INCHES) : SEMI-WET BACK
BOILER HORSEPOWER 30 40 50 60 70 80 100 125 150 200 250
  HEATING SURFACE FIRESIDE SQ. FT. 150 200 250 300 350 400 500 625 750 1000 1250  
STEAM OUTPUT FROM & @212°F LB/HR 1035 1380 1725 2070 2415 2760 3450 4313 5175 6900 8625
GROSS OUTPUT   MBH 1004 1339 1674 2009 2343 2678 3348 4184 5021 6695 8369
FIRING RATE, GAS 1,000 BTU/CF CFH 1260 1680 2100 2520 2940 3360 4200 5250 6300 8400 10500
FIRING RATE, LP GAS 91,500 BTU GPH 13.8 18.4 23 27.5 32 36.7 46 57 69 92 115
FIRING RATE, No.2 oil 140,00O BTU GPH 9 12 15 18 21 24 29.9 37.4 45 60 75
FIRING RATE, #5 & #6 OIL 150,000 BTU GPH 8.4 11.2 14 16.8 19.6 22.4 28 35 42 56 70
A *NOTE: 1 STEAM OUTLET SIZE 150 PSI IN 1 1/2 2 2 1/2 2 1/2 3 3 4 4 4 4 6 A
A *NOTE: 2 STEAM OUTLET SIZE 15 PSI IN 4 4 4 6 6 6 8 8 8 8 10 A
B *NOTE: 2 SUPPLY SIZE 30 PSI IN 4 4 4 6 6 6 8 8 8 8 10 B
C *NOTE: 2 RETURN SIZE 30 PSI       IN 4 4 4 4 4 4 6 6 6 6 8 C
D FEEDWATER CONNECTION   IN 3/4 3/4 3/4 1 1 1 1/4 1 1/4 1 1/4 1 1/4 1 1/2 1 1/2 D
E BOTTOM BLOWDOWN SIZE HIGH PRESS. IN 1 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 E
E BOTTOM BLOWDOWN SIZE LOW PRESS. & HW IN 1 1/4 1 1/4 1 1/4 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 E
F STACK OUTLET SIZE O.D.   IN 10 10 10 12 12 12 14 14 16 16 18 F
G FURNACE O.D.   IN 14 14 16 18 18 18 22 26 30 30 34 G
H SHELL I.D.   IN 40 40 44 48 48 48 54 60 66 70 79 H
I SUPPLY HEIGHT   IN 60 60 64 68 68 68 75 82 88 91 104 I
J WIDTH WITHOUT TRIM   IN 46 46 50 54 54 54 60 67 73 76 85 J
K WIDTH WITH TRIM   IN 58 58 62 66 66 66 72 79 84 88 97 K
L SKID WIDTH   IN 34 34 36 40 40 40 44 48 51 56 60 L
M END OF SKID TO FRONT PLATE   IN 13 1/2 14 1/4 15 1/4 15 1/4 15 1/4 15 1/4 21 3/4 25 1/4 25 1/4 34 1/4 28 1/8 M
N VESSEL SHELL TO FLOOR   IN 12 12 12 12 12 12 14 15 15 14 18 N
O SKID LENGTH   IN 81 99 102 102 102 114 114 132 147 168 168 O
P STACK OUTLET HEIGHT   IN 59 59 63 67 67 67 75 82 88 91 104 P
Q BLOWDOWN LOCATIONS   IN 36 41 32 30 30 30 30-50 33-56 34-93 34-105 36-109 Q
R STEAM OUTLET LOCATION (15 PSI & UP) FROM C/L OF STACK IN 38 41 39 1/2 48 48 57 55 55 67 71 72 R
S SUPPLY LOCATION FROM FRONT PLATE IN 20 21 33 38 38 44 33 32 34 46 51 S
T RETURN LOCATION C/L TO C/L IN 39 54 45 48 48 54 58 70 82 80 74 T
U BURNER PROJECTION FROM FRONT PLATE IN 32 32 36 36 36 39 1/2 39 44 44 45 45 U
V TUBE REMOVABLE FRONT IN 61 78 81 82 82 94 88 100 116 128 131 V
W LENGTH FRONT TO REAR BOILER VESSEL IN 79 96 100 106 106 118 116 128 147 3/8 162 168 W
X APPROX. OVERALL LENGTH (WITH BURNER) STD. BURNER IN 111 128 136 142 142 158 157 174 193 208 214 X
  APPROX. SHIPPING WEIGHT 150 PSI LBS 3500 4100 4700 6000 6200 7000 9500 10400 13500 16600 22000  
APPROX. SHIPPING WEIGHT 15 & 30 PSI LBS 3400 4000 4500 5700 5900 6200 7200 9400 12500 13700 20500
WATER CAPACITY @ NWL   GAL 215 272 324 378 359 416 484 681 945 1126 1489
WATER CAPACITY FLOODED   GAL 252 319 382 434 415 479 578 793 1130 1350 1850
  BOILER HORSEPOWER 30 40 50 60 70 80 100 125 150 200 250  

BOILER SPECIFICATIONS (ALL DIMENSIONS ARE IN INCHES) - CONTINUED
  BOILER HORSEPOWER 300 350 400 500 600 700 750 800 900 1000 1200 1500  
  HEATING SURFACE FIRESIDE SQ. FT. 1500 1750 2000 2500 3000 3500 3750 4000 4500 5000 6000 7500  
STEAM OUTPUT FROM & @212°F LB/HR 10350 12075 13800 17250 20700 24150 25875 27600 31050 34500 41400 51750
GROSS OUTPUT   MBH 10043 11716 13390 16738 200085 23432 25106 26780 30128 33475 40170 50213
FIRING RATE, GAS 1,000 BTU/CF CFH 12600 14700 16800 21000 25200 29400 31500 33600 37800 42000 50400 63000
FIRING RATE, LP GAS 91,500 BTU GPH 138 160 184 230 275 320 344 368 413 460 550 688
FIRING RATE, No.2 oil 140,00O BTU GPH 90 105 120 150 180 210 225 240 270 300 360 450
FIRING RATE, #5 & #6 OIL 150,000 BTU GPH 84 98 112 140 168 196 210 224 252 280 336 420
A *NOTE: 1 STEAM OUTLET SIZE 150 PSI IN 6 6 6 6 8 8 8 8 8 8 10 10 A
A *NOTE: 2 STEAM OUTLET SIZE 15 PSI IN 10 10 10 10 12 12 12 12 14 14 14 14 A
B *NOTE: 2 SUPPLY SIZE 30 PSI IN 10 10 10 10 12 12 12 12 12 12 14 14 B
C *NOTE: 2 RETURN SIZE 30 PSI IN 8 8 8 8 8 10 10 10 12 12 14 14 C
D FEEDWATER CONNECTION   IN 2 2 2 2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 D
E BOTTOM BLOWDOWN SIZE HIGH PRESS. IN 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 2 2 2 2 E
E BOTTOM BLOWDOWN SIZE LOW PRESS. & HW IN 2 2 2 2 2 2 2 2 2 2 2 1/2 2 1/2 E
F STACK OUTLET SIZE O.D.   IN 20 20 24 24 28 30 30 30 30 30 32 32 F
G FURNACE O.D.   IN 34 34 38 44 46 52 52 52 52 52 56 56 G
H SHELL I.D.   IN 84 84 90 96 102 115 115 115 120 120 132 136 H
I SUPPLY HEIGHT   IN 109 109 115 121 127 140 140 140 146 1/4 146 1/4 159 163 I
J WIDTH WITHOUT TRIM   IN 91 91 97 103 109 122 122 122 128 128 140 144 J
K WIDTH WITH TRIM   IN 103 103 108 114 121 132 132 132 138 138 150 156 K
L SKID WIDTH   IN 64 64 70 76 78 88 88 88 92 92 104 114 L
M END OF SKID TO FRONT PLATE   IN 28 5/8 34 5/8 30 5/8 35 5/8 48 5/8 41 5/8 41 5/8 42 5/8 48 5/8 52 5/8 55 5/8 54 1/2 M
N VESSEL SHELL TO FLOOR   IN 18 18 18 18 18 18 18 18 18 18 18 18 N
O SKID LENGTH   IN 174 204 198 222 252 228 240 252 261 288 294 330 O
P STACK OUTLET HEIGHT   IN 109 109 115 121 127 140 1/4 140 1/4 140 1/4 146 146 159 163 P
Q BLOWDOWN LOCATIONS   IN 36-96 42-110 48-98 48-120 49-159 48-144 48-156 50-165 50-168 50-191 58-186 60-192 Q
R STEAM OUTLET LOCATION (15 PSI & UP) FROM C/L OF STACK IN 70 83 93 1/2 93 97 87 90 91 100 106 124 142 R
S SUPPLY LOCATION FROM FRONT PLATE IN 46 54 54 57 66 61 61 64 64 71 74 74 S
T RETURN LOCATION C/L TO C/L IN 88 95 95 102 110 108 116 126 126 135 137 159 T
U BURNER PROJECTION FROM FRONT PLATE IN 45 47 52 65 67 67 70 69 75 75 72 84 U
V TUBE REMOVABLE FRONT IN 132 156 156 178 191 173 185 199 201 224 224 258 V
W LENGTH FRONT TO REAR BOILER VESSEL IN 171 195 195 219 236 222 234 247 250 273 278 315 W
X APPROX. OVERALL LENGTH (WITH BURNER) STD. BURNER IN 219 245 251 290 306 292 307 319 328 351 350 402 X
  APPROX. SHIPPING WEIGHT 150 PSI LBS 25000 27600 30000 37000 42200 51500 54000 56500 61500 66500 82000 100000  
APPROX. SHIPPING WEIGHT 15 & 30 PSI LBS 23000 25600 28000 35000 4000 49000 51500 54000 57500 62500 77000 93000
WATER CAPACITY @ NWL   GAL 1628 1925 2250 2779 3707 3019 3758 4017 4504 5010 5762 7121
WATER CAPACITY FLOODED   GAL 2147 2530 2829 3557 4611 4838 5161 5513 6218 6908 8498 10480
  BOILER HORSEPOWER 300 350 400 500 600 700 750 800 900 1000 1200 1500  
PRODUCT: 500 Series Fire Tube Wetback Boiler

Custom manufacturer of engineered packaged boilers and systems, boiler controls and accessories. Major supplier of wood, gas, coal, solid-fuel, and oil-fired steam and hot water boilers, fire-tube & water-tube, and feedwater equipment for all heating & process applications including industrial, dry cleaning, hospital, educational, municipal, military, public and private commercial requirements.

Durability
Built in accordance with the ASME Code, the wet back design has proven to give much longer useful life cycles than dry back boilers.

Quality
Each unit is tested and inspected, and is registered with the National Board of Boiler and Pressure Vessel Inspectors.

Design
Hurst Boiler utilizes state of the art computer design techniques in every boiler. This accounts for accurate calculations of construction materials and optimum utilization of the boiler’s performance criteria.

High Fuel Efficiency
The Series 500 is designed for optimum fuel efficiency. The introduction of the fourth pass extracts every BTU of spent energy possible that would otherwise be vented to the stack of dry back boilers.

Low Maintenance
There are no refractory doors to replace or maintain. Elimination of these will result in thousands of dollars in savings.

Tube Sheets
The wet back has independent rear tube sheets with uniform temperatures. Four pass dry back boilers have tube sheets with large temperature variations resulting in premature tube failure and cracks in the tube sheets.

Easy Access
Since there is no large refractory rear door, one man can easily remove the rear cover plates for access to the tubes. Front doors can be opened without removing burner components or controls.

Compact
With computer aided design, Hurst has made the wet back a space saving workhorse without sacrificing the principle of 5 sq. ft. of heating surface per BHP.

Combustion
Hurst uses top name-brand burner components with proven reliability. Every unit is boiler/burner compatible and tested at the factory prior to shipment.


WET BACK ADVANTAGE

Dry backs are subject to deteriorating rear refractory, leaking baffles, leaking door seals, and often found with a heat-stressed rear tubesheet. Fragile refractory baffling and door seals will require continuous monitoring, maintenance, and replacement, costing thousands of dollars in materials and specialized labor cost over the life of the boiler. In addition, broken baffles and leaking seals will short-circuit boiler efficiency up until repairs can be made, and downtime during repairs can bring your production process to a halt.

All of those frustrating problems have been designed out of the Hurst Series 500 Wetback. It has a full wet back radiant heat transfer area that promotes superior internal water circulation and rapid heat absorption. Separate rear tubesheets allow each pass of tubes to expand and contract at its own rate without tube-to-sheet stress.Tubes are mechanically rolled, flared and beaded, making any tube service a simple matter. The only rear refractory is a 18 inch plug which allows access to the furnace for inspection.

Four Pass Wet Back Packaged Scotch Boilers

Standard Steam Trim

  • Operating & high limit pressure control
  • Water column with gauge glass combination low water cut-off & pump control
  • Probe type auxiliary low water cut-off with manual reset
  • Water column drain valve
  • Safety relief valve(s) per ASME Code
  • Steam Gauge
  • Stack Thermometer

Standard Water Trim

  • Operating & high limit temperature control
  • Low water cut-off control with manual reset
  • Combination pressure, temperature gauge
  • Hot water return baffle for shock resistance
  • Safety relief valve(s) per ASME Code
  • Stack Thermometer
PASS ILLUSTRATION
PASS ILLUSTRATION
PASS ILLUSTRATION
PASS ILLUSTRATION
Four Pass Wet Back Packaged Scotch Boilers

Available in Steam at 15 PSIG. up to 300 PSIG.
Available in Hot Water at 30 PSIG. up to 160 PSIG. @ 250°F.

  • Four-pass wet back design eliminates refractory baffles between flue gas passes.
  • Minimum maintenance with rugged construction for extra-long life.
  • U.L. listed packaged burner for firing gas, oil and combination gas/oil.
  • Factory tested and checked for optimum operating efficiency.
The Series 500, four pass dry back boilers are designed for optimum fuel efficiency.