| DEAERATOR SPECIFICATIONS (ALL DIMENSIONS ARE IN INCHES) | |||||||||||||
| OXY-MISER MODEL NO. | OM-5 | OM-7 | OM-10 | OM-12 | OM-14 | OM-16 | OM-19 | OM-22 | OM-26 | ||||
| WEIGHT | TANK/TRIM | LBS | 2400 | 2400 | 2700 | 2700 | 3000 | 3000 | 4000 | 4000 | 4500 | ||
| CAPACITY | LBS/HR | 5,000 | 7,000 | 10,000 | 12,000 | 14,000 | 16,000 | 19,000 | 22,000 | 26,000 | |||
| WATER CAPACITY | @ OVERFLOW | GAL | 268 | 268 | 331 | 331 | 456 | 456 | 789 | 789 | 957 | ||
| WATER CAPACITY | @ NWL | GAL | 118 | 118 | 141 | 141 | 189 | 189 | 285 | 285 | 347 | ||
| WATER CAPACITY (W/DOME) | FLOODED | GAL | 354 | 354 | 424 | 424 | 565 | 565 | 877 | 877 | 1033 | ||
| A | TANK DIAMETER | IN | 42 | 42 | 42 | 42 | 42 | 42 | 48 | 48 | 48 | A | |
| B | TANK LENGTH | IN | 48 | 48 | 60 | 60 | 84 | 84 | 96 | 96 | 120 | B | |
| C | OVERALL LENGTH | BARE VESSEL | IN | 70 | 70 | 81 1/2 | 81 1/2 | 105 | 105 | 118 | 118 | 142 | C |
| D | SUPPORT STAND LENGTH | IN | 46 | 46 | 54 | 54 | 72 | 72 | 84 | 84 | 96 | D | |
| E | SADDLE WIDTH | IN | 36 | 36 | 36 | 36 | 36 | 36 | 42 | 42 | 42 | E | |
| F | STEAM INLET | 150#-FLNG | IN | 4 | 4 | 4 | 4 | 6 | 6 | 6 | 6 | 6 | F |
| G | WATER OUTLET | 150#-FLNG | IN | 3 | 3 | 3 | 3 | 4 | 4 | 4 | 4 | 6 | G |
| H | TANK DRAIN | IN | 1 1/4 | 1 1/4 | 1 1/4 | 1 1/4 | 1 1/2 | 1 1/2 | 2 | 2 | 2 | H | |
| I | OVERFLOW | IN | 1 1/4 | 1 1/4 | 1 1/2 | 1 1/2 | 1 1/2 | 1 1/2 | 2 | 2 | 2 | I | |
| J | CONDENSATE RETURN | IN | 2 | 2 | 2 | 2 | 2 1/2 | 2 1/2 | 3 | 3 | 3 | J | |
| K | INLET WATER | IN | 1 1/4 | 1 1/4 | 1 1/4 | 1 1/4 | 1 1/2 | 1 1/2 | 1 1/2 | 1 1/2 | 1 1/2 | K | |
| L | DOME DIAMETER | IN | 12 | 12 | 12 | 12 | 14 | 14 | 16 | 16 | 16 | L | |
| M | STEAM PURGE VENT | IN | 3/4 | 3/4 | 3/4 | 3/4 | 1 | 1 | 1 | 1 | 1 | M | |
| N | TANK HEIGHT | FROM SUPPORT | IN | 66 | 66 | 66 | 66 | 72 | 72 | 76 | 76 | 76 | N |
| O | BASE OF SADDLE TO C/L OF TANK | IN | 27 | 27 | 27 | 27 | 29 | 29 | 30 | 30 | 30 | O | |
| P | C/L TO OVERFLOW | IN | 7 1/2 | 7 1/2 | 9 | 9 | 9 | 9 | 9 1/2 | 9 1/2 | 9 1/2 | P | |
| Q | HD. TO VENT CONNECTION | IN | 24 | 24 | 30 | 30 | 42 | 42 | 48 | 48 | 60 | Q | |
| OXY-MISER MODEL NO. | OM-5 | OM-7 | OM-10 | OM-12 | OM-14 | OM-16 | OM-19 | OM-22 | OM-26 | ||||
| DEAERATOR SPECIFICATIONS (ALL DIMENSIONS ARE IN INCHES) - CONTINUED | ||||||||||||||
| OXY-MISER MODEL NO. | OM-30 | OM-35 | OM-40 | OM-50 | OM-60 | OM-80 | OM-100 | OM-125 | OM-150 | OM-200 | ||||
| WEIGHT | TANK/TRIM | LBS | 4500 | 4750 | 5700 | 7300 | 8000 | 8800 | 9500 | 10500 | 11500 | 14000 | ||
| CAPACITY | LBS/HR | 30,000 | 35,000 | 40,000 | 50,000 | 60,000 | 80,000 | 100,000 | 125,000 | 150,000 | 200,000 | |||
| WATER CAPACITY | @ OVERFLOW | GAL | 957 | 1025 | 1224 | 1600 | 1931 | 2421 | 2717 | 3810 | 4354 | 5796 | ||
| WATER CAPACITY | @ NWL | GAL | 347 | 365 | 444 | 560 | 679 | 848 | 954 | 1324 | 1517 | 1998 | ||
| WATER CAPACITY (W/DOME) | FLOODED | GAL | 1033 | 1091 | 1305 | 1673 | 2022 | 2521 | 2832 | 3935 | 4499 | 5956 | ||
| A | TANK DIAMETER | IN | 48 | 54 | 54 | 66 | 66 | 72 | 72 | 84 | 84 | 96 | A | |
| B | TANK LENGTH | IN | 120 | 96 | 120 | 96 | 120 | 126 | 144 | 144 | 168 | 168 | B | |
| C | OVERALL LENGTH | BARE VESSEL | IN | 142 | 123 1/2 | 147 1/2 | 126 1/4 | 148 1/4 | 156 | 174 | 179 | 203 | 207 | C |
| D | SUPPORT STAND LENGTH | IN | 96 | 84 | 102 | 84 | 108 | 108 | 120 | 132 | 128 | 132 | D | |
| E | SADDLE WIDTH | IN | 42 | 48 | 48 | 56 | 56 | 60 | 60 | 66 | 66 | 78 | E | |
| F | STEAM INLET | 150#-FLNG | IN | 6 | 6 | 6 | 8 | 8 | 10 | 10 | 10 | 10 | 10 | F |
| G | WATER OUTLET | 150#-FLNG | IN | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 8 | 8 | 8 | G |
| H | TANK DRAIN | IN | 2 | 2 | 2 | 2 | 2 1/2 | 2 1/2 | 2 1/2 | 2 1/2 | 3 | 2 1/2 | H | |
| I | OVERFLOW | IN | 2 | 2 | 2 | 3 | 3 | 3 | 3 | 3 | 3 | 6 | I | |
| J | CONDENSATE RETURN | IN | 3 | 3 | 3 | 4 | 4 | 4 | 4 | 6 | 6 | 6 | J | |
| K | INLET WATER | IN | 1 1/2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 1/2 | 2 1/2 | 4 | K | |
| L | DOME DIAMETER | IN | 16 | 18 | 18 | 20 | 20 | 20 | 20 | 24 | 24 | 30 | L | |
| M | STEAM PURGE VENT | IN | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | M | |
| N | TANK HEIGHT | FROM SUPPORT | IN | 76 | 86 | 86 | 101 | 101 | 111 | 111 | 124 | 124 | 135 | N |
| O | BASE OF SADDLE TO C/L OF TANK | IN | 30 | 35 | 35 | 41 | 41 | 44 | 44 | 50 | 50 | 56 | O | |
| P | C/L TO OVERFLOW | IN | 9 1/2 | 11 3/4 | 11 3/4 | 16 | 16 | 16 | 16 | 17 | 17 | 24 | P | |
| Q | HD. TO VENT CONNECTION | IN | 60 | 51 | 60 | 48 | 60 | 60 | 72 | 72 | 84 | 84 | Q | |
| OXY-MISER MODEL NO. | OM-30 | OM-35 | OM-40 | OM-50 | OM-60 | OM-80 | OM-100 | OM-125 | OM-150 | OM-200 | ||||
|
|


Available from 5,000 to 200,000 LBS/HR The Hurst Oxy-Miser deaerating boiler feedwater system eliminates the need of expensive oxygen scavenger chemicals and also offers the following advantages:
WHY DEAERATE? The use of deaerators has long been used in power plants and water tube type boilers, primarily because they remove undissolved oxygen and raise the temperature of the feedwater. These advantages are important today for firetube boilers as well, due to higher capital investments. Operating costs can be reduced by recovering flash steam when returned by high temperature condensate. This feature also raises the feedwater temperature, thus requiring less boiler fuel to convert the feedwater to useable steam. Boiler tubes, condensate lines, and process piping have a much longer useful life by eliminating the pitting action of untreated water. This advantage alone justifies the cost of an OXY-MISER deaerator. HOW DOES IT WORK? Undeaerated fresh water is fed into the deaerator through the inlet water connection. This water passes through the steam-filled heating and venting section. The water temperature is raised and many of the undissolved gases are released. As the water passes through the assembly, it flows to a scrubber section where final deaeration is accomplished by scrubbing the water with oxygen free steam. This steam is induced through a stainless steel spray valve assembly which causes the high velocity steam to break the water down to a fine mist through a violent scrubbing action. The deaerated water spills over to the tanks storage compartment for use by the boiler, and the gases are vented to the atmosphere. STANDARD EQUIPMENT
|