The leading engineering solution provider in Bangladesh with local competence.
Sizes 30 to 1,000 gallons (Larger Sizes on Request) For all types of steam boilers with pressures to 300 psig. Systems are available in single, dual, triple and quad pump configurations.
SPECIFICATIONS (ALL DIMENSIONS ARE IN INCHES)
BOILER HP TANK CAPACITY (GAL.) (A) LENGTH (B) WIDTH * (C) HEIGHT 15-150 PSI * (C) HEIGHT 200-250 PSI * (C) HEIGHT 300 PSI ** (D) WATER SUPPLY (E) COND. RETURN (F) VENT (G) OVER FLOW (H) DRAIN SHIPPING WIEGHT 150 PSI
15-30 30 30 19 60 68 69 1/2 2 2 1 1/2 3/4 550
40-60 60 36 25 67 73 86 1/2 2 1 1/2 1 1/4 3/4 650
70-80 80 46 29 67 75 86 1/2 2 1 1/2 1 1/4 3/4 700
100 100 48 26 74 76 87 3/4 2 1 1/2 1 1/4 3/4 825
125-150 150 48 31 79 90 93 3/4 2 1 1/2 2 1 1100
200 200 60 34 88 93 96 3/4 2 1/2 1 1/2 2 1 1250
250 250 72 35 89 93 96 3/4 2 1/2 1 1/2 2 1 1400
300 300 72 38 92 96 99 3/4 2 1/2 2 2 1 1730
350 350 84 38 92 96 99 3/4 2 1/2 2 1/2 2 1 1835
400 400 72 44 98 102 114 3/4 3 2 1/2 2 1 1/4 2050
500 500 84 44 104 110 114 3/4 3 2 1/2 2 1 1/4 2300
600 600 84 48 108 114 118 3/4 3 2 1/2 2 1 1/4 2450
700-800 800 114 48 120 118 125 3/4 3 2 1/2 2 1 1/4 2940
900-1000 100 96 58 130 135 135 (2) 3/4 3 3 3 1 1/2 4200

STANDARD PUMP CONFIGURATION
BOILER HP 15 PSI PUMP# 15 PSI Motor HP. NPSH Req'd 150 PSI PUMP# 150 PSI Motor HP. NPSH Req'd 200 PSI PUMP# 200 PSI Motor HP. NPSH Req'd ***
250 PSI PUMP#
***
250 PSI Motor HP.
NPSH Req'd ***
300 PSI PUMP#
***
300 PSI Motor HP.
NPSH Req'd
15-30 CR1-2 U 1/3 2.7 CR1-13 U 1 1/2 2.7 CR1-17 U 2 2.7 CR1-21 U 3 2.7 CR1-27 U 3 2.7
40-60 CR1-2 U 1/3 3.4 CR1-15 U 2 3.4 CR1-19 U 2 3.4 CR1-23 U 3 3.4 CR1-27 U 3 3.5
70-80 CR3-3 UK 1/2 1.4 CR3-13 UK 3 1.4 CR3-19 UK 3 1.4 CR3-23 UK 5 1.4 CR5-24 UK 7.5 2
100 CR3-3 UK 1/2 1.4 CR3-15 UK 3 1.4 CR3-19 UK 3 1.4 CR3-23 UK 5 1.4 CR5-24 UK 7.5 2.4
125-150 CR3-3 UK 1/2 2.1 CR3-17 UK 3 2.1 CR3-23 UK 5 2.1 CR5-22 UK 7.5 3.6 CR8-140 U 15 1.9
200 CR5-3 UK 1 3.2 CR5-13 UK 5 3.2 CR5-18 UK 7.5 3.2 CR5-22 UK 7.5 3.2 CR8-160 U 15 1.9
250 CR5-3 UK 1 3.8 CR5-14 UK 5 3.8 CR5-20 UK 7.5 3.8 CR5-24 UK 7.5 3.8 CR8-160 U 15 2
300 CR5-3 UK 1 4.1 CR5-16 UK 5 4.1 CR5-22 UK 7.5 4.1 CR8-140 U 15 2.2 CR8-160 U 15 2.2
350 CR8-20/1 U 3/4 2.8 CR8-100 U 7 1/2 2.8 CR8-120 U 10 2.8 CR8-140 U 15 2.8 CR8-160 U 15 2.8
400 CR8-20/1 U 3/4 3.7 CR8-100 U 7 1/2 3.7 CR8-120 U 10 3.7 CR8-140 U 15 3.7 CR16-120 U 25 1.6
500 CR8-30/2 UK 2 4.1 CR16-60 U 15 2.1 CR16-80 U 15 2.2 CR16-100 U 20 2.1 CR16-120 U 25 2.1
600 CR16-30/2 U 5 3.5 CR16-70 U 15 3.5 CR16-80 U 15 3.5 CR16-100 U 20 3.5 CR16-120 U 25 3.5
700-800 CR32-1-1 U 3 6.4 CR16-70 UK 15 6 CR16-100 UK 20 6 CR16-120 UK 25 6 CR32-9-2 U 40 6.4
900-1000 CR32-1-1 U 3 7.4 CR32-5 U 20 7.4 CR32-7-2 U 25 7.4 CR32-8-2 U 30 7.4 CR32-9 U 40 7.4
PRODUCT: Feedmiser

PASS ILLUSTRATION
PASS ILLUSTRATION
PASS ILLUSTRATION
PASS ILLUSTRATION

Sizes 30 to 1,000 gallons (Larger Sizes on Request) For all types of steam boilers with pressures to 300 psig. Systems are available in single, dual, triple and quad pump configurations.Sizes 30 to 1,000 gallons (Larger Sizes on Request) For all types of steam boilers with pressures to 300 psig.

SUGGESTED SPECIFICATIONS

The Hurst Feedmiser Automatic Return System provides storage for water make-up and return condensate from the system loop. The system consists of an elevated tank mounted boilers.

When equipped with optional trim, the Feedmiser provides a quality, heavy duty packaged unit fully assembled and ready to install. These units are factory assembled with pre-wired control panel, and fully piped pumps along with all the neccessary fittings and valves. Consider the optional automatic steam preheater. When incorporated into the system, feedwater temperature can be maintained at 210° F. At this high temperature, oxygen and carbon dioxide are released, reducing corrosion problems in the boiler and piping system. Systems are available in single, dual, triple and quad pump configurations and custom orders are welcome.

The following trim shall be factory installed on each system:

  1. Automatic, internal float actuated fresh water make-up valve assembly. Water gauge glass set with bronze shut-off cocks and drain. Tank drain valve, brass gate. Bi-metallic water thermometer.
  2. Pump suction piping with shut-off valve and strainer.

Typical Optional Equipment:

  • Control panel with motor starters & breakers.
  • Pump function lights, selector switches.
  • Diffuser tube for extra high temperature condensate return .
  • High and low water level alarms.
  • Pump alternator switches.
  • Magnesium corrosion rod.
  • Epoxy lining Manhole openings (200 gallon & larger).
  • Electric solenoid valve make-up water assembly. Steam operated feedwater preheater.
  • Discharge pressure gauges.
timer