150# STEAM 4VT CYCLONE SERIES SPECIFICATIONS
  BOILER HORSEPOWER 6 10 15 20 25 30 40 50 60 70 80 100  
  STEAM OUTPUT FROM & AT 212°F LBS./HR.
KG./HR.
207
94
345
156
518
235
69
0313
863
391
1035
469
1380
626
1725
782
2070
939
2415
1095
2760
1252
3450
1565
 
GROSS OUTPUT    (MBH), BTU X 1000
KCAL X 1000
201
51
335
84
502
127
670
169
837
211
1004
253
1339
337
1674
422
2009
506
2343
590
2678
675
3348
844
INPUT REQUIRED   BTU X 1000
KCAL X 1000
251
63.3
418
105
628
158
837
211
1046
264
1255
316
1674
422
2092
527
2511
633
2929
738
3348
844
4184
1054
FIRING RATE, NAT. GAS 1000BTU/FT3 FT 3/HR.
M 3/HR.
251
7.1
418
11.8
628
17.8
837
23.7
1046
29.6
1255
35.5
1674
47.4
2092
59.2
2511
71.1
2929
82.9
3348
94.8
4184
118.5
FIRING RATE, LP. GAS 91,500 BTU/GAL. GPH
LPH
2.7
10.4
4.6
17.3
6.9
26
9.1
34.6
11.4
43.3
13.7
51.9
18.3
69.2
22.9
86.6
27.4
103.9
32
121.2
36.6
138.5
45.7
173.1
FIRING RATE, #2 OIL 140.000 BTU GPH
LPH
1.8
6.8
3
11.3
4.5
17
6
22.6
7.5
28.3
9
33.9
12
45.3
14.9
56.6
17.9
67.9
20.9
79.2
23.9
90.5
29.9
113.1
A STEAM OUTLET HIGH PRESS. IN.
MM
1
25
1
25
1
25
1
25
1.25
32
1.5
38
2
51
2.5
64
2.5
64
2.5
64
2.5
64
3
76
A
A STEAM OUTLET LOW PRESS. IN.
MM
2
51
2
51
2
51
3
76
3
76
4
102
4
102
6
152
6
152
6
152
6
152
6
152
A
B BLOWDOWN HIGH PRESS. IN.
MM
1
25
1
25
1
25
1
25
1
25
1.25
32
1.25
32
1.25
32
1.25
32
1.25
32
1.25
32
1.25
32
B
B BLOWDOWN LOW PRESS. IN.
MM
1
25
1
25
1
25
1
25
1
25
1.25
32
1.25
32
1.25
32
1.25
32
1.5
38
1.5
38
1.5
38
B
C FEEDWATER   IN.
MM
0.75
19
0.75
19
0.75
19
0.75
19
0.75
19
1
25
1
25
1
25
1
25
1
25
1
25
1.25
32
C
D STACK DIA.   IN.
MM
8
203
8
203
8
203
8
203
8
203
10
254
12
305
12
305
12
305
14
356
14
356
14
356
D
E STACK HEIGHT   IN.
MM
52
1321
52
1321
58
1473
64
1626
64
1626
63
1600
73
1854
83
2108
83
2108
82
2083
82
2083
82
2083
E
F WIDTH WITHOUT TRIM   IN.
MM
35.2
894
35.2
894
35.2
894
35.2
894
35.2
894
41
1041
50
1270
59
1499
59
1499
68
1727
68
1727
78.2
1986
F
G WIDTH WITH TRIM   IN.
MM
42
1067
42
1067
42
1067
42
1067
42
1067
47
1194
55
1397
63
1600
63
1600
72
1829
72
1829
82
2083
G
H OVERALL HEIGHT   IN.
MM
79
2007
79
2007
85
2159
85
2159
85
2159
85
2159
93
2362
105
2667
105
2667
106
2692
106
2692
110
2794
H
I HEIGHT WITHOUT TRIM   IN.
MM
65
1651
65
1651
71
1803
77
1956
77
1956
77
1956
88
2235
99
2515
99
2515
99
2515
99
2515
99
2515
I
J LENGTH   IN.
MM
60
1524
60
1524
60
1524
60
1524
60
1524
78
1981
87
2210
115
2921
115
2921
120
3048
120
3048
127
3226
J
  WATER CAP. @ NWL   GALS.
LITERS
48
182
48
182
54
204
54
204
54
204
73
276
118
447
151
572
151
572
187
708
187
708
274
1037
 
WATER CAP. FLOODED   GALS.
LITERS
62
235
62
235
68
257
79
299
79
299
113
428
208
787
313
1185
313
1185
440
1665
440
1665
581
2199
SHIPPING WEIGHT    LBS.
KG.
1700
771
1700
771
1850
839
1900
862
1900
862
2300
1043
3900
1769
5500
2495
5500
2495
7600
3447
7600
3447
9100
4128
  BOILER HORSEPOWER 6 10 15 20 25 30 40 50 60 70 80 100  
PRODUCT: 4VT Cyclone Series (Steam)

STANDARD FEATURES

INSPECTION ACCESS

  • The waterside openings are located in the most effective positions. The lower handholes offer far better access for both cleanout and inspection.
  • These more functional locations avoid the obstructing handhole “tunnels” used by our competitors.
  • The top opening offers a strategic view of the furnace crown sheet.

MORE STEAM STORAGE

  • Capacity to handle swing and spike loads - quick recovery - quick response.
  • The larger steam-release surface is calmer, reducing carry over of unevaporated water.
  • The resulting drier steam also reduces system scaling.
  • In addition, dry steam helps to eliminate unnecessary extra condensate. Energy and fuel are saved. Longer life results.

FOUR-PASS DESIGN

  • The gases leaving the furnace are split four ways and travel through four individual serpentine fin passages to the stack outlet.
  • Each quarter of the heat
    travels its own four-pass path (see illustration below).
  • Heat transfers evenly to the fins and boiler shell, eliminating the metal stress due to uneven heat transfer common in other designs.

This illustration shows the progression of four gas paths around the circumference of the boiler shell.

  1. Primary-pass in furnace pipe.
  2. Second-pass follows path through fins along outside of shell.
  3. Third-pass follows path through fins along outside of shell.
  4. Fourth-pass follows path through fins along outside of shell, then merges together to exit exhaust stack.
Four Pass High-Pressure Tubeless Boilers

OPTIONS AND ALTERNATIVES

  • We specialize in customizing your boiler. The Cyclone can be equipped to suit a wide variety of installations and specifications. We will help direct you to the most cost-effective models and features.

SIMPLE INSTALLATION

  • Unit is skid mounted for easy handling.
  • Factory wired with wiring schematic included in the manual.
  • Efficient and space saving layout.

AVAILABLE ACCESSORIES

  • The Cyclone is available in a complete package with an optional compact boiler-mounted feedwater system for a finished wired and piped, ready-to-fire unit.
  • Blowdown separators are also available.

TURBULENT FLAME

  • Heat is forced down, with the fire whirling and spinning against its natural flow. This pattern enhances recirculation, mixing and heat transfer, driving more energy into the water for greater fuel-to-steam efficiency.

RELIABILITY

  • The furnace crown is water cooled, eliminating troublesome refractory breakdown inherent in units of inferior design.
  • No fire tubes, water coils or “in the fire” mud rings to burn out.

“EYE HIGH” BURNER

  • No step ladder is needed to service.
  • No bending over or sitting on the floor.
  • The air intake is located in the center of the unit so dust is not pulled from the floor.

Steam outlet valve, slow opening blowdown valve, feedwater shut off valve, and check valves included on boilers through 30Hp.

DURABILITY

  • Fire does not pass under the bottom mud ring, eliminating the blistering that occurs with other designs.
  • Cooler furnace gases are located at the bottom of the vessel where scale is most likely to occur. Baking of scale is alleviated.

EASIER SERVICE

  • Fireside fin access in top and bottom.
  • Access opening above feedwater inlet for easy cleaning.
  • Thoughtfully engineered with the owner in mind.
  • No heavy doors or covers to complicate service procedures.

SAFETY

  • Electrical components are located away from the floor, helping eliminate the possibility of water coming in contact with electricity.
  • Boiler built to ASME Section 1, High Pressure Boiler Code.
  • CSD-1 approved.
  • Burner/Boiler UL Packaged.
PASS ILLUSTRATION
PASS ILLUSTRATION
PASS ILLUSTRATION
PASS ILLUSTRATION

The Cyclone is available in a complete package with an optional compact boiler-mounted feedwater system for a finished wired and piped, ready-to-fire unit.4VT Series Packaged Vertical Design

Four Pass High-Pressure Tubeless Boilers

STANDARD STEAM TRIM

  • Steam pressure gauge with syphon and test cockCombination low water cutoff and pump control with water column blowdown valveProbe auxiliary low water cutoff and relayASME safety relief valveOperating and high limit pressure controlsSteam outlet valve, slow opening blowdown valve, feedwater shut off valve, and check valves included on boilers through 30Hp.
  • Burner/Boiler UL Packaged
timer