The leading engineering solution provider in Bangladesh with local competence.
The Cyclone Hot Water Boilers provide for exceptionally high efficiencies, lower fuel costs, and extremely rugged construction. Steam outlet valve, slow opening blowdown valve, feedwater shut off valve, and check valves included on boilers through 30Hp.
LEFT SIDE VIEW FRONT VIEW TOP VIEW
CYCLONE SERIES SPECIFICATIONS
  BOILER HORSEPOWER 6 10 15 20 25 30 40 50 60 70 80 100  
  GROSS OUTPUT (MBH), BTU X 1000
KCAL X 1000
201
51
335
84
502
127
670
169
837
211
1004
253
1339
337
1674
422
2009
506
2343
590
2678
675
3348
844
 
INPUT REQUIRED BTU X 1000
KCAL X 1000
251
63.3
418
105
628
158
837
211
1046
264
1255
316
1674
422
2092
527
2511
633
2929
738
3348
844
4184
1054
FIRING RATE, NAT. GAS 1000 BTU/FT3 FT 3/HR.
M 3/HR.
251
7.1
418
11.8
628
17.8
837
23.7
1046
29.6
1255
35.5
1674
47.4
2092
59.2
2511
71.1
2929
82.9
3348
94.8
4184
118.5
FIRING RATE, LP. GAS 91,500 BTU/GAL. GPH
LPH
2.7
10.4
4.6
17.3
6.9
26
9.1
34.6
11.4
43.3
13.7
51.9
18.3
69.2
22.9
86.6
27.4
103.9
32
121.2
36.6
138.5
45.7
173.1
FIRING RATE, No.2 oil 140.000 BTU/GAL. GPH
LPH
1.8
6.8
3
11.3
4.5
17
6
22.6
7.5
28.3
9
33.9
12
45.3
14.9
56.6
17.9
67.9
20.9
79.2
23.9
90.5
29.9
113.1
A OUTLET SIZE IN.
MM
2
51
2
51
2
51
3
76
3
76
4
102
4
102
6
152
6
152
6
152
6
152
6
152
A
B RETURN SIZE IN.
MM
2
51
2
51
2
51
2.5
64
2.5
64
3
76
3
76
4
102
4
102
4
102
4
102
4
102
B
C DRAIN SIZE IN.
MM
1
25
1
25
1
25
1
25
1
25
1.25
32
1.25
32
1.25
32
1.25
32
1.5
38
1.5
38
1.5
38
C
D STACK DIA. IN.
MM
8
203
8
203
8
203
8
203
8
203
10
254
12
305
12
305
12
305
14
356
14
356
14
356
D
E STACK HEIGHT IN.
MM
52
1321
52
1321
58
1473
64
1626
64
1626
63
1600
73
1854
83
2108
83
2108
82
2083
82
2083
82
2083
E
F WIDTH WITHOUT TRIM IN.
MM
35.2
894
35.2
894
35.2
894
35.2
894
35.2
894
41
1041
50
1270
59
1499
59
1499
68
1727
68
1727
78.2
1986
F
G WIDTH WITH TRIM IN.
MM
42
1067
42
1067
42
1067
42
1067
42
1067
47
1194
55
1397
63
1600
63
1600
72
1829
72
1829
82
2083
G
H OVERALL HEIGHT IN.
MM
70
1778
70
1778
76
1930
82
2083
82
2083
82
2083
93
2362
105
2667
105
2667
106
2692
106
2692
106
2692
H
I HEIGHT WITHOUT TRIM IN.
MM
65
1651
65
1651
71
1803
77
1956
77
1956
77
1956
88
2235
98
2489
98
2489
98
2489
98
2489
98
2489
I
J LENGTH IN.
MM
60
1524
60
1524
60
1524
60
1524
60
1524
78
1981
87
2210
115
2921
115
2921
120
3048
120
3048
127
3226
J
  WATER CAPACITY GALS.
LITERS
62
235
62
235
68
257
79
299
79
299
113
428
208
787
313
1185
313
1185
440
1665
440
1665
591
2237
 
SHIPPING WEIGHT LBS.
KG.
1600
726
1600
726
1750
794
1800
816
1800
816
2175
987
3775
1712
5300
2404
5300
2404
7300
3311
7300
3311
8700
3946
  BOILER HORSEPOWER   6 10 15 20 25 30 40 50 60 70 80 100  
PRODUCT: 4VT Cyclone Series (Hot Water)

Steam outlet valve, slow opening blowdown valve, feedwater shut off valve, and check valves included on boilers through 30Hp.
PASS ILLUSTRATION
PASS ILLUSTRATION
PASS ILLUSTRATION
PASS ILLUSTRATION

The Cyclone Hot Water Boilers provide for exceptionally high efficiencies, lower fuel costs, and extremely rugged construction.

Other features include:

  • Compact space saving vertical design
  • Four-Pass Design
  • Shock Proof, no tubes to loosen or burn out
  • Convenient access to “eye high” burner
  • Solid State controls for trouble free operation
  • Factory assembled, fully automatic
  • UL and ASME CSD - 1
  • Simple and inexpensive to install
  • Standard design pressure of 30 PSI
    Optional to 160 PSI, 250° F
The Cyclone Hot Water Boilers provide for exceptionally high efficiencies, lower fuel costs, and extremely rugged construction.